Fire Fighting Systems in Hyderabad

Engineered for absolute reliability. We design and install high-performance hydrant, sprinkler, and pumping systems for industrial and commercial projects in Hyderabad.

Authoritative Fire Protection Infrastructure

SMB Engineering Services is a premier fire fighting contractor in Hyderabad. We specialize in the end-to-end execution of fire protection systems, from initial hydraulic design to final commissioning and Fire NOC support. Our systems strictly adhere to NBC 2016 Part 4 and relevant Bureau of Indian Standards (BIS) codes.

Hydrant Systems vs Sprinkler Systems

A robust fire safety plan involves a combination of manual and automatic systems.

  • External & Internal Hydrants: These are the "heavy artillery" of fire fighting. Strategically placed valves allow firefighters to connect hoses and deliver high-volume water directly to the fire. Essential for all industrial units in Jeedimetla and Cherlapally.
  • Automatic Sprinklers: These provide immediate, localized suppression. A heat-sensitive bulb shatters at a specific temperature (usually 68°C), releasing water directly where the fire started. This is the gold standard for high-rise residential and commercial buildings in Gachibowli.

Pumping Station Design

The pumping station is the "heart" of the fire fighting system. A compliant pump house in Hyderabad typically includes:

  • Main Electrical Pump: The primary water source.
  • Standby Diesel Pump: Ensures operation during power failures.
  • Jockey Pump: To maintain system pressure and prevent main pump wear.
  • CPVC/MS Pipeline: Engineered for specific flow rates and pressures.

IS 3844 Compliance & Safety Protocols

Compliance isn't just about passing inspections; it's about system performance under stress. We follow IS 3844 for internal hydrants and IS 15105 for sprinkler installations. This includes ensuring correct pipe sizing, proper selection of hose reels, and installation of fire department inlets.

Maintenance & Compliance Schedule

Weekly

  • • Run test of fire pumps
  • • Check diesel levels
  • • Visual inspection of hydrant valves

Quarterly

  • • Flushing of hydrant lines
  • • Testing of alarm valves
  • • Check for pipe corrosion

Annual

  • • Full hydraulic flow test
  • • Painting & refurbishing
  • • Submission of Compliance Form 16

Fire Fighting System FAQs

What is the primary difference between Hydrant and Sprinkler systems?

A Hydrant system is manually operated by firefighters or trained personnel using hoses, while a Sprinkler system is automatic and triggers when heat is detected, providing immediate localized suppression.

Which Indian Standards (IS) govern hydrant systems?

The installation and maintenance of hydrant systems are primarily governed by IS 3844 (Code of practice for installation and maintenance of internal fire hydrants and hose reels) and IS 13039.

What is the role of a Jockey Pump in a fire fighting system?

A jockey pump is a small pump that maintains the static pressure in the hydrant and sprinkler pipelines. It prevents the main fire pumps from starting unnecessarily during minor pressure drops or leaks.

How often should fire pumps be tested?

Fire pumps should be tested weekly (running test) to ensure they start correctly. A full flow test (performance test) should be conducted annually as per NBC and NFPA guidelines.

What building types in Hyderabad require automatic sprinklers?

As per NBC 2016, sprinklers are mandatory for buildings over 15 meters (high-rise), basements over 200 sqm, and specific occupancies like malls, hospitals, and industrial warehouses.

Do you provide design drawings for fire fighting systems?

Yes, we provide complete hydraulic calculations and system design drawings (CAD) compliant with Telangana State Fire Services requirements for Fire NOC approval.

What are 'Wet Risers' and 'Downcomers'?

A wet riser is a vertical pipe constantly charged with water under pressure. A downcomer is a vertical pipe connected to an overhead tank, typically used for buildings under 30 meters height.

Do you install fire fighting systems in Hyderabad?

Yes, SMB Engineering Services provides complete fire fighting system installation and commissioning in Hyderabad.

Are your fire fighting systems IS compliant?

Yes, all our fire fighting systems are designed as per IS and NFPA standards.

Building a New Facility in Hyderabad?

Ensure your fire safety starts on the right foot with a compliant design. Contact our senior engineers for a consultation.

Consult an Expert